Permit Number: T04CM04690
Parcel: 117060210

Address:
605 E 9TH ST 1M

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04690
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
10/21/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
10/22/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show that the water piping is adequate to supply the proposed washers. Reference Section 610.4, UPC 1994.
10/22/2004 ROBERT SHERRY WATER REVIEW Approved
10/22/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Run the dryer exhausts independently. Reference Section 504.1, IMC 2000.
10/25/2004 ANY BUILDING-COMMERCIAL REVIEW Passed
10/25/2004 GERRY KOZIOL WWM REVIEW Approved
10/25/2004 JIM EGAN FIRE REVIEW Approved
10/25/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM04690 DENIED 10/22/04
1. Change all references from NEC 1999 to NEC 2002. This has been in effect since July 1, 2004.
2. Electrical plan shows 4 receptacles on H-13. Account for such on panel schedule. It appears that it will be necessary to rebalance load to avoid overloading Phase A.
3. Fixture schedule and cut sheet needed for new luminaires.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/25/2004 LISA LESNY OUT TO CUSTOMER Completed