Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04690
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/21/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 10/21/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 10/22/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show that the water piping is adequate to supply the proposed washers. Reference Section 610.4, UPC 1994. |
| 10/22/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/22/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Run the dryer exhausts independently. Reference Section 504.1, IMC 2000. |
| 10/25/2004 | ANY | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 10/25/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/25/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/25/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM04690 DENIED 10/22/04 1. Change all references from NEC 1999 to NEC 2002. This has been in effect since July 1, 2004. 2. Electrical plan shows 4 receptacles on H-13. Account for such on panel schedule. It appears that it will be necessary to rebalance load to avoid overloading Phase A. 3. Fixture schedule and cut sheet needed for new luminaires. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/25/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |