Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04677
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/21/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/21/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/21/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 10/21/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/21/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 10/21/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the air flow in Private Toilet to comply with the requirements of Section 403.2.1 (3), IMC 2000. |
| 10/21/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM04677 DENIED 10/21/04 1. Plans show load on Ckt 25. Account for load on panel schedule. 2. Mechanical shows AC-1 and AC-2 as single phase equipment. Electrical provides 3-phase power. Coordinate with Mechanical and clarify. 3. Mechanical shows AC-1 and AC-2 as 35.2 MCA. #10 conductor and 30A CB appears to be undersized. |
| 10/21/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 10/26/2004 | EGRANT1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/26/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |