Permit Number: T04CM04677
Parcel: 11005553A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04677
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2004 JIM EGAN FIRE REVIEW Approved
10/21/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/21/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Needs Review
10/21/2004 ROBERT SHERRY WATER REVIEW Approved
10/21/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
10/21/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the air flow in Private Toilet to comply with the requirements of Section 403.2.1 (3), IMC 2000.
10/21/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM04677 DENIED 10/21/04
1. Plans show load on Ckt 25. Account for load on panel schedule.
2. Mechanical shows AC-1 and AC-2 as single phase equipment. Electrical provides 3-phase power. Coordinate with Mechanical and clarify.
3. Mechanical shows AC-1 and AC-2 as 35.2 MCA. #10 conductor and 30A CB appears to be undersized.
10/21/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
10/26/2004 EGRANT1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/26/2004 BETH GRANT OUT TO CUSTOMER Completed