Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM04663
Parcel: 12810082B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04663
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2004 JIM EGAN FIRE REVIEW Approved
10/29/2004 Robert Suba ELECTRICAL-COMMERCIAL REVIEW Approved
11/05/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC 2000.
2. Provide a cut sheet of the convection oven being installed in the warming kitchen to show that a Type II exhaust hood is not required.
3. If not already installed, provide smoke detectors in the return air duct, upstream of any outside air connections, for all air distribution systems with a capacity greater than 2,000 CFM. Reference Section 606.1, IMC.
4. Replot sheet M2.1 to show the missing information in the details and schedules.
5. Provide information to show that a machinery room is not required for the refrigeration equipment located inside the building. Reference Section 1104.2, IMC 2000.
6. Show how adequate access is being provided for the equipment located in the attic space. Reference Section 306.3, IMC 2000.
7. Provide cut sheets for the gas-fired generator and show that the installation of the generator complies with the requirements of NFPA 37 and the manufacturer's installation requirements. Reference Section 915.2, IMC 2000.
11/05/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Appliances to be directly connected to the water supply system (e.g. ice machine and glass washer) that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994.
2. Resize the reduced pressure backflow preventor to comply to Section 610.2, UPC 1994.
3. Limit the water velocity to less than 8 fps for the PVC piping. Reference Section A 6.1, UPC 1994 and IAPMO IS 8-92.
4. Coordinate the fixture schedule and the plumbing plan; the fixture schedule indicates 3 hose bibbs but only one hose bibb is shown on the plans.
5. Coordinate the CW, HW isometric with the plumbing plan; the 3-compartment sink is not shown on the isometric.
6. Clarify why one compartment of the 3-compartment sink is not indirectly wasted. Reference Section 801.2, UPC 1994.
7. Include the water fixture units for the ice machine in the demand calculations. Reference Table 6-3, UPC 1994.
8. Show the location of the upper terminal cleanout for the existing building drain that runs under the new back office. Reference Section 707.4, UPC 1994.
9. Provide an upper terminal cleanout for the floor sink located in the retail area. Reference Section 707.4, UPC 1994.
10. Provide cleanouts for the hand sinks and for the 3-compartment sink. Reference Section 707.4, UPC 1994.
11. Include water and waste riser diagrams for the kitchen and bar fixtures.
12. Provide a gas piping schematic that includes the new and existing piping.
13. Provide insulation for the recirculating hot water system that complies with Section 804.5, IECC 2000.
14. Provide controls for the water heating system that will comply with the requirements of Sections 804.3 and 804.6, IECC 2000.
11/05/2004 ROBERT SHERRY WATER REVIEW Approved
11/18/2004 GERRY KOZIOL WWM REVIEW Approved
12/07/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 12-07-04
ACTIVITY NUMBER: T04CM04663
PROJECT NAME: 58 DEGREES AND HOLDING CO.
PROJECT ADDRESS: 5340 E. BROADWAY BLVD.
ARCHITECT / ENGINEER: BMG INC.
PROJECT REVIEWER: CHRISTY FOREMAN



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) IT APPEARS THE CODE ANALYSIS INACCURATE. SEE 302.3.1 NON-SEPERATED USE. MOST RESTRICTIVE USE SHALL APPLY TO THE ENTIRE BLDG.
2) SECTION 307 CLARIFY STORAGE AREA / ALCOHOLIC BEVERAGE QUANTITIES PER TABLE 307.7 (1) SEE NOTE C.
3) ALLOWABLE AREA CALCULATION APPEARS TO BE INACCURATE. SEE TABLE 503 AND SECTION 506. BUILDINGS ON THE SAME LOT SHALL BE REGULATED AS SEPARATE BUILDINGS OR SHALL BE CONSIDERED AS PORTIONS OF ONE BUILDING IF THE HEIGHT OF EACH BUILDING AND THE AGGREGATE AREA OF BUILDINGS ARE WITHIN THE LIMITATIONS OF TABLE 503 AS MODIFIED BY SECTIONS 504 & 506.
4) DIMENSIONED SITE PLAN
SHOW MEETING 1105 ACCESSIBLE ENTRANCE REQUIREMENTS
SHOW MEETING 1106 PARKING AND PASSENGER LOADING FACILITIES.
5) CLARIFY TABLE 602 FIRE RESISTIVE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPERATION DISTANCE.
6) CLARIFY 704.3 BUILDING ON THE SAME LOT - FOR THE PURPOSES OF DETERMINING THE REQUIRED WALL AND OPENING PROTECTION AND ROOF COVERING REQUIREMENTS, BUILDING ON THE SAME LOT SHALL BE ASSUMED TO HAVE AN IMAGINARY LINE BETWEEN THEM.
7) TABLE 704.8 - JUSTIFY BUILDING OPENINGS.
8) 1008.1.8.2 CLARIFY DOOR HARDWARE HEIGHT.
9) SHOW LOCATION OF SECTION 1/A1.1 ON FLOOR PLAN.
10) DEMOLITION NOTE 5 - EXISTING TOILET ROOM REMAINS. FLOOR PLAN A2.1 SHOWS NEW LAYOUT. PLEASE CLARIFY.
11) CLARIFY LOCATION OF MECH / FLOOR FRAMING WITH ARCHITECTURAL & STRUCTURAL PLANS. IT APPEARS NOTE 26 ON SHT. A2.1 LOCATES A GENERATOR ON AREA NOT STRUCTURALLY DESIGNED BY STRUCTURAL ENGINEER.
12) COORDINATE ROOF MECH. PLAN, FOUNDATION PLAN, AND FLOOR FRAMING PLAN ON SHTS2.1 WITH ARCHITECTURAL PLAN SHT A2.1.
13) CLARIFY INTERIOR WALL FRAMING WITH DETAILS AND WALL SECTIONS.
14) SHT. S1.1 SHOWS WOOD STUD FRAMING AND CONNECTORS. SHT A4.1 SHOWS MTL STUD FRAMING. PLEASE CLARIFY.
15) DIMENSION FLOOR PLAN AND EXTERIOR STAIR ENTRANCE - LOCATE STAIR DETAIL ON SHT A4.1 ON SHT. A2.1.
16) FRAMING DETAILS FOR STORAGE LOCKER ENTRANCE.
17) WALL SECTION AT ENTRY BETWEEN RETAIL SALE AND LOUNGE /WINE.
18) JUSTIFY FIXTURE COUNT PER TABLE 2902.1 AND MIXED OCCUPANCY USE.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/14/2004 TAMI ACHONG OUT TO CUSTOMER Completed
12/14/2004 ANGIE SHOFFSTALL REJECT SHELF Completed