Permit Number: T04CM04654
Parcel: 125050530

Address:
700 N WILSON AV

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T04CM04654
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2004 Jim Egan FIRE REVIEW Approved
10/29/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Provide calculations to show that the level gutter on the Ramada can handle 3" of rain per hour. Include the effect of the vertical wall adjacent to the Ramada in the calculations. Reference Sections D 3.2 and D 3.4, UPC 1994.
2. Coordinate the water riser diagram with the plumbing floor plan. Reference Section 103.2.3, UPC 1994.
3. Clarify the size of the water supply to the new building; 1-1/2" on sheet 15.3 and 2" on sheet 1.0. Reference Section 103.2.3, UPC 1994.
4. Show how the additional water demand from the activity building will not overload the existing water supply system. Reference Section 103.2.3, UPC 1994.
5. Revise the size of the water pipes to the water closets to correspond to the submitted water calculations.
6. The building drain design shown on sheet 15.3 is coordinated with option 2 for the building sewer of sheet 1.0. Show how the design would be modified if option 1 for the building sewer is selected. Reference Section 103.2.3, UPC 1994.
7. The rim elevation of the next upstream sanitary manhole (59.36') is higher than the first floor elevation (56.72'). Provide a backwater valve per Section 710.1, UPC 1994 if option 2 is selected.
8. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 804.4, IECC 2000.
10/29/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/29/2004 ROBERT SHERRY WATER REVIEW Approved
11/03/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Show the installation of the Grounding Electrode required by NEC 250.32 (A) for "Two or More Buildings Supplied from a Common Service." Connected as specified in 250.32 (B) (1) and Exhibit 250.18 in the Handbook.
2. Provide sufficient information to demonstrate that the Water Heater, as specified in the Plumbing Fixture Specifications, is cord-connected. Otherwise, please provide A disconnect per NEC 422.30.
3. Main Service Load Summary does not appear to include the 43.7 KVA Adjusted Service Demand. Please clarify.
4. City of Tucson does not allow the use of the "Up-Over-Down" method used in Item 4 Fault Current Considerations. Please provide fault calculations for AFC at new panel.
11/18/2004 Gerry Koziol WWM REVIEW Approved
11/22/2004 Christy Foreman BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 11/26/04
ACTIVITY NUMBER: T04CM04654
PROJECT NAME: ACTIVITY BLDG. SAM HUGHES ELEMENTARY
PROJECT ADDRESS: 700 N. WILSON AVE.
ARCHITECT / ENGINEER: CDG ARCHITECTS / VALERIE HUDSON
PROJECT REVIEWER: CHRISTY FOREMAN
PHONE: 7901-5550 X1108
EMAIL: CFOREMA1@CI.TUCSON.AZ.US

TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1. SHT. 3.3, DETAIL 11 SPECIFY SIMPSON JOIST HANGER.
2. OCCUPANT LOAD = 355 THEREFORE 178 MALE AND 178 FEMALE.
178/125 = 1.4 W.C MALE THEREFORE = 2 WATER CLOSETS OR 1 W.C. & 1 URINAL
178/65 = 2.7 W.C. FEMALE THEREFORE = 3 WATER CLOSETS
TOTAL FIXTURES (MALE, FEMALE, & UNISEX) = 25 + 2 (NEW) = 27
TOTAL FIXURES REQUIRED = 24 (EXISTING) + 5 (NEW) = 29 (TOTAL FIXTURES REQUIRED)

THEREFORE FIXTURE COUNT IS STILL SHORT 2 FIXTURES.

I SPOKE WITH DAVE MANN AND HE WAS WILLING TO ACCOMMODATE LESS FIXTURES FOR THE NEW BUILDING IF THE TOTAL FIXTURE COUNT ON CAMPUS MADE UP FOR THE ONES LACKING. THEREFORE ADDITIONAL FIXTURES STILL NEED TO BE PROVIDED.
11/23/2004 DAVID RIVERA ZONING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/29/2004 TAMI ACHONG OUT TO CUSTOMER Completed
11/29/2004 ANGIE SHOFFSTALL REJECT SHELF Completed