Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T04CM04654
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/20/2004 | Jim Egan | FIRE | REVIEW | Approved | |
| 10/29/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide calculations to show that the level gutter on the Ramada can handle 3" of rain per hour. Include the effect of the vertical wall adjacent to the Ramada in the calculations. Reference Sections D 3.2 and D 3.4, UPC 1994. 2. Coordinate the water riser diagram with the plumbing floor plan. Reference Section 103.2.3, UPC 1994. 3. Clarify the size of the water supply to the new building; 1-1/2" on sheet 15.3 and 2" on sheet 1.0. Reference Section 103.2.3, UPC 1994. 4. Show how the additional water demand from the activity building will not overload the existing water supply system. Reference Section 103.2.3, UPC 1994. 5. Revise the size of the water pipes to the water closets to correspond to the submitted water calculations. 6. The building drain design shown on sheet 15.3 is coordinated with option 2 for the building sewer of sheet 1.0. Show how the design would be modified if option 1 for the building sewer is selected. Reference Section 103.2.3, UPC 1994. 7. The rim elevation of the next upstream sanitary manhole (59.36') is higher than the first floor elevation (56.72'). Provide a backwater valve per Section 710.1, UPC 1994 if option 2 is selected. 8. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference Section 804.4, IECC 2000. |
| 10/29/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/29/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/03/2004 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Show the installation of the Grounding Electrode required by NEC 250.32 (A) for "Two or More Buildings Supplied from a Common Service." Connected as specified in 250.32 (B) (1) and Exhibit 250.18 in the Handbook. 2. Provide sufficient information to demonstrate that the Water Heater, as specified in the Plumbing Fixture Specifications, is cord-connected. Otherwise, please provide A disconnect per NEC 422.30. 3. Main Service Load Summary does not appear to include the 43.7 KVA Adjusted Service Demand. Please clarify. 4. City of Tucson does not allow the use of the "Up-Over-Down" method used in Item 4 Fault Current Considerations. Please provide fault calculations for AFC at new panel. |
| 11/18/2004 | Gerry Koziol | WWM | REVIEW | Approved | |
| 11/22/2004 | Christy Foreman | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 11/26/04 ACTIVITY NUMBER: T04CM04654 PROJECT NAME: ACTIVITY BLDG. SAM HUGHES ELEMENTARY PROJECT ADDRESS: 700 N. WILSON AVE. ARCHITECT / ENGINEER: CDG ARCHITECTS / VALERIE HUDSON PROJECT REVIEWER: CHRISTY FOREMAN PHONE: 7901-5550 X1108 EMAIL: CFOREMA1@CI.TUCSON.AZ.US TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1. SHT. 3.3, DETAIL 11 SPECIFY SIMPSON JOIST HANGER. 2. OCCUPANT LOAD = 355 THEREFORE 178 MALE AND 178 FEMALE. 178/125 = 1.4 W.C MALE THEREFORE = 2 WATER CLOSETS OR 1 W.C. & 1 URINAL 178/65 = 2.7 W.C. FEMALE THEREFORE = 3 WATER CLOSETS TOTAL FIXTURES (MALE, FEMALE, & UNISEX) = 25 + 2 (NEW) = 27 TOTAL FIXURES REQUIRED = 24 (EXISTING) + 5 (NEW) = 29 (TOTAL FIXTURES REQUIRED) THEREFORE FIXTURE COUNT IS STILL SHORT 2 FIXTURES. I SPOKE WITH DAVE MANN AND HE WAS WILLING TO ACCOMMODATE LESS FIXTURES FOR THE NEW BUILDING IF THE TOTAL FIXTURE COUNT ON CAMPUS MADE UP FOR THE ONES LACKING. THEREFORE ADDITIONAL FIXTURES STILL NEED TO BE PROVIDED. |
| 11/23/2004 | DAVID RIVERA | ZONING | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/29/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 11/29/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |