| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/10/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/10/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. The waste and vent diagram indicates both a hair trap and a p-trap for the shampoo sinks; this appears to be double trapping. Show how the design complies with the requirements of Section 1004.0, UPC 1994. 2. Comment not completely addressed. Show how the water piping has been sized. Refernce Section 610.1, UPC 1994. |
| 11/10/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/10/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/18/2004 | LLESNY1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/18/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |