Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04648
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/02/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM04648 DENIED 11/02/04 1. Ckt 5, with 10 existing 4-bulb 32W luminaires, would have well over a KVA of load, even before the addition of the new load. Please re-evaluate. 2. Please re-evaluate styling salon circuits for loading. With blow dryers, I would suggest greater demand than 180 VA per outset. 3. Please consider sign and track lighting circuits as continuous load if they are to operate for greater than three continuous hours. |
| 11/02/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Termination of the HVAC condensate over a splash block on the roof is not approved. Reference Section 307.2.1, IMC 2000, as amended by the City of Tucson. 2. Clarify the status of the rooftop unit: new or existing? |
| 11/02/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. If the rooftop air conditioner is new, provide design for the gas piping to the unit. 2. The waste and vent diagram indicates both a hair trap and a p-trap for the shampoo sinks; this appears to be double trapping. Show how the design complies with the requirements of Section 1004.0, UPC 1994. 3. Show how the water piping has been sized. Refernce Section 610.1, UPC 1994. 4. Specify the plumbing materials to be used. 5. Provide a description of all plumbing fixtures to show that they comply with the requirements of Section 401.1, UPC 1994. |
| 11/03/2004 | ANY | ENGINEERING | REVIEW | Approved | |
| 11/03/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 11/03/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) RESTROOM FACILITY COMPLY WITH CODE SECTION 1210.1. 2) CLARIFY WHERE NEW WALLS ARE AND WALL SECTIONS ARE CUT. |
| 11/10/2004 | LLESNY1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/10/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |