Permit Number: T04CM04648
Parcel: 10321671B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04648
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM04648 DENIED 11/02/04
1. Ckt 5, with 10 existing 4-bulb 32W luminaires, would have well over a KVA of load, even before the addition of the new load. Please re-evaluate.
2. Please re-evaluate styling salon circuits for loading. With blow dryers, I would suggest greater demand than 180 VA per outset.
3. Please consider sign and track lighting circuits as continuous load if they are to operate for greater than three continuous hours.
11/02/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Termination of the HVAC condensate over a splash block on the roof is not approved. Reference Section 307.2.1, IMC 2000, as amended by the City of Tucson.
2. Clarify the status of the rooftop unit: new or existing?
11/02/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. If the rooftop air conditioner is new, provide design for the gas piping to the unit.
2. The waste and vent diagram indicates both a hair trap and a p-trap for the shampoo sinks; this appears to be double trapping. Show how the design complies with the requirements of Section 1004.0, UPC 1994.
3. Show how the water piping has been sized. Refernce Section 610.1, UPC 1994.
4. Specify the plumbing materials to be used.
5. Provide a description of all plumbing fixtures to show that they comply with the requirements of Section 401.1, UPC 1994.
11/03/2004 ANY ENGINEERING REVIEW Approved
11/03/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
11/03/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) RESTROOM FACILITY COMPLY WITH CODE SECTION 1210.1.
2) CLARIFY WHERE NEW WALLS ARE AND WALL SECTIONS ARE CUT.
11/10/2004 LLESNY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/10/2004 LISA LESNY OUT TO CUSTOMER Completed