Permit Review Detail
Review Status: Completed
Review Details: REVISION - WALK THRU
Permit Number - T04CM04643
Review Name: REVISION - WALK THRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/16/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. If the proposed ice machine is not equipped with an integral air gap or backflow protection, provide backflow protection for the ice machine. 2. Include the demand (or fixture units) for the ice machine in the water demand calculations. 3. Show that the minimum available operating pressure for the building is adequate for the ice machine (including the pressure requirement of the backflow device if required). 4. Provide listing information for the ice machine. |
| 12/20/2004 | LLESNY1 | WWM | REVIEW | Needs Review |