Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04643
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/19/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/19/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/19/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/19/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/19/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide mechanical plan. Reference Section 106.3.1, IMC 2000. 2. Show how the warehouse, offices, restrooms, and retail space meet the ventilation requirements of Section 403.3, IMC 2000. |
| 10/20/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM04643 DENIED 10/20/04 1. Heat pump at 26A would have (26) (1.73) (208) = 9360 VA, or 3120 per phase. Please check Ckt 2,4,6 and the other motor loads on the panel schedule. 2. Count 25% for the largest motor on on panel schedule. 3. On panel schedule, there is a notation for continuous duty at 1.25%. Please indicate which circuits are considered as such, and adjust load calculations accordingly as necessary. |
| 10/25/2004 | LLESNY1 | WWM | REVIEW | Needs Review | |
| 10/25/2004 | LLESNY1 | ZONING | REVIEW | Needs Review | |
| 10/25/2004 | LLESNY1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/25/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |