Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM04631
Parcel: 11460019B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04631
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2004 Robert Suba ELECTRICAL-COMMERCIAL REVIEW Approved
11/18/2004 ROBERT SHERRY WATER REVIEW Approved
11/18/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the furniture, fixture, and equipment schedule (sheet P-1) with the fixture connection schedule on sheet P-3. Reference Section 103.2.3, UPC 1994.
2. Provide water pressure and water pipe sizing calculations using Table 6-4, UPC 1994. Reference Section 610.4, UPC 1994.
3. Re-plot sheet P2 so that the existing piping in the riser diagrams is legible. Reference Section 103.2.3, UPC 1994.
4. The note on sheet P2 regarding backflow protection is incorrect. Double check valves are only appropriate for devices with low-hazard (pollution) exposures. Water-cooled compressors, for example, have a high-hazard (contamination) exposure. Reference Section 603, UPC 1994.
5. Show all of the directly connected equipment and specify the required backflow device for each. Reference Section 103.2.3, UPC 1994.
11/18/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information for the water-cooled freezer to show how much water is being used and its refrigeration capacity. Reference Section 106.3.1, IMC 2000.
2. Provide the refrigeration capacity, refrigerant type, and the amount of refrigerant for the walk-in freezer and cooler. Reference Section 106.3.1, IMC 2000.
11/23/2004 Gerry Koziol WWM REVIEW Approved
12/07/2004 Doug Laakso BUILDING-COMMERCIAL REVIEW Denied .. T04CM04631 .. 7113 E TANQUE VERDE ROAD .. DGL .. 12/7/04 ..


S1. Clarify valuation : justify $12000 submitted or revise valuation.
S2. Provide a revised and completed code review checklist , occupancy ?, separation? , area calculation?.
S3. Provide a second accessible toilet room as both female and male is required for this A2 occupancy, with an occupant load of 31.
S4. Provide a vertical grab bar per ANSI A117.1-2003 ed Section #604.5 and fig #605.1 , also locate the toilet paper dispenser 7"-9" in front of water closet per fig #604.7 .
S5. Provide note on drawing addressing accessibility of site and buildings re: conformance with IBC Section 3409 and ANSI A117.1-2003 ed..
S6. Provide structural calculations to address new equipment placed on roof.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/09/2004 TAMI ACHONG OUT TO CUSTOMER Completed
12/09/2004 ANGIE SHOFFSTALL REJECT SHELF Completed