Permit Number: T04CM04612
Parcel: 10711121A

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T04CM04612
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/22/2005 BLANCA ESPINO ENGINEERING REVIEW Denied Site Plan
1. Please include a response letter with the next submittal that states how all comments have been addressed. Include plans/redlines from previous plan submittal.

2. Indicate roof slope and location of downspouts. D.S. 2-02.2.1.A.6 Add note, "All roof spouts will be routed under any adjacent sidewalk." Sidewalks shall be flood free for all storm discharges of up to a ten (10) year flood event. D.S. 2-08.3.1 & 4.1.E

3. Indicate existing and future sight visibility triangles. Near side is 345', Far side is 125'. D.S. 2-02.2.1.A.10 Fort Lowell Road is an MS&R and requires 100-feet of future right-of-way with an eleven-foot sidewalk area with a six-foot sidewalk. Correct and revise.

4. Indicate and label proposed signage.

5. Fully dimensioned loading space maneuvering area. D.S. 2-02.2.1.A.14

6. Indicate drainage patterns, proposed finish floor elevation(s) and finish grades. Do not obstruct offsite to onsite flows. D.S. 2-02.2.1.A.16

7. A grading review/permit is required. Submit a grading plan for review.

8. The access driveway shall be aligned with the existing driveway across the street. Dimension distance between adjacent driveways. Correct and revise. D.S. 2-02.2.1.A.18 Contact Dale Kelch with COT/DOT-Traffic Engineering, 5th floor Public Works Building for approval of driveway location.

9. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways and utility lines. D.S. 2-02.2.1.A.21 The minimum curb return for an arterial street to a PAAL is 25 feet. Correct and revise. D.S. 3-01.3.2.C, D.S. 3-01.10.Figure 6 & TAMG.5.4-6

10. Indicate contour intervals along with the north arrow and scale. This should be placed together. D.S. 2-02.2.1.A.1 Indicate and label existing topographic contours at intervals not exceeding two (2) feet or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number. D.S. 2-02.2.1.A.23

11. Demonstrate and dimension refuse vehicle maneuverability and access to refuse enclosure.
05/13/2005 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. A street landscape border, is a area running the full length of the street property line bounding the site except for points of ingress-egress, Billboards can not be located within street landscape border per DS 2-06.3.4.C.

2. Any vegetation higher than thirty (30) inches must be located outside of the sight visibility triangles per 3.7.3.4. Cassia nemophila, Dasyliron wheelerii and Caesalpina mexicana will typically grow in excess of 4', acceptable substations would be Lecophyllum candidum (Thunder Cloud) and Agave geminiflora. Replace plants or revise plans as necessary.
05/16/2005 DAN CASTRO ZONING REVIEW Denied COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The existing billboard is located within future right-of-way. The billboard will have to be removed or relocated to an area in compliance with LUC regulations at time of road widening. A stamp, which explains this requirement will be added to the plan by the Zoning Review Section. (D.S. 2-02.2.1.A.19)

2. Label and dimension future curb location along Ft. Lowell Road. Face of future curb shall be located eleven (11) feet in front of the future right of way line. (D.S. 2-02.2.1.A.21)

3. Identify the paved area south of the proposed building. If this area is used for outdoor storage or display, it must be added to the vehicle parking calculation.

3. All requested changes must be made to the site and landscape plans.

4. Review of this plan by the Zoning Review Section may be done over the counter. Please contact Dan Castro to set an appointment.

If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608 ext. 1180. An appointment is required to discuss these comments in person.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/09/2005 KMEDINA1 OUT TO CUSTOMER Completed