Permit Number: T04CM04605
Parcel: 14122001D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04605
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
10/28/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/28/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM04605 DENIED 10/28/04
Submit electrical design, including the items below:
1. Electrical site drawing with locations of all equpiment, such as new tower, motor disconnects, existing and new electrical circuits, power source.
2. Specify sizing of electrical conduit, conductor, and overcurrent protective devices.
3. Provide power requirements for equipment, and overall feeder/service load calculation, as appropriate.
4. Specify conduit, conductor and overcurrent protective device type.
10/28/2004 ROBERT SHERRY WATER REVIEW Approved
10/28/2004 ANY BUILDING-COMMERCIAL REVIEW Needs Review
10/28/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed