Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM04588
Parcel: 13510150R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04588
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2004 JIM EGAN FIRE REVIEW Approved
10/14/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/14/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
10/14/2004 ROBERT SHERRY WATER REVIEW Approved
10/14/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
10/14/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/14/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied DENIED 10/14/04

1. Add power requirements for new accent lights to fixture schedule.
2. Circuit A-5, with 24 LF of track lighting, shall be counted as (75) (24) = 1800 VA, which is well above the 950 VA on the panel schedule. Then add the accent lights. Count all as continuous load in load calculation. NEC 220.12 (B).
3. Identify power receptacle on power pole.
4. Circuit A-6, with 5 duplex and 2 quad receptacles, would have (9) (180) = 1620 VA, plus the load on the power pole per Comment #3 above.
5. Panel load calculations shall use demand factors of 1.25 for all continuous loads and largest motor on feeder.
11/08/2004 DROBEY1 WWM REVIEW Needs Review
11/08/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved