Permit Number: T04CM04584
Parcel: 105102430

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04584
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
10/14/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide expansion tank for the water heater.
2. If the new water heater is not equipped with integral heat traps, provide heat traps and insulate the first 8 feet of cold water and hot water piping from the water heater. Reference Sections 804.4 and 804.5, IECC 2000.
10/14/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
10/14/2004 ROBERT SHERRY WATER REVIEW Approved
10/14/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
10/14/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the ventilation calculations to comply with Section 403.3.2, IMC 2000.
10/18/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM04584 DENIED 10/18/04
Project address on Permit card is 4485 N First #121. Addresses on meters are 625 E Wetmore. This suite #115 on line diagram but 121 on Permit Application. Pls clarify.
10/22/2004 LLESNY1 WWM REVIEW Needs Review
10/22/2004 LLESNY1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/22/2004 LISA LESNY OUT TO CUSTOMER Completed