Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04584
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/14/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 10/14/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide expansion tank for the water heater. 2. If the new water heater is not equipped with integral heat traps, provide heat traps and insulate the first 8 feet of cold water and hot water piping from the water heater. Reference Sections 804.4 and 804.5, IECC 2000. |
| 10/14/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/14/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/14/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 10/14/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the ventilation calculations to comply with Section 403.3.2, IMC 2000. |
| 10/18/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM04584 DENIED 10/18/04 Project address on Permit card is 4485 N First #121. Addresses on meters are 625 E Wetmore. This suite #115 on line diagram but 121 on Permit Application. Pls clarify. |
| 10/22/2004 | LLESNY1 | WWM | REVIEW | Needs Review | |
| 10/22/2004 | LLESNY1 | FIRE | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/22/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |