Permit Number: T04CM04581
Parcel: 12105013B

Review Status: Completed

Review Details: OTHER

Permit Number - T04CM04581
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM04581 DENIED 10/27/04
1. Lighting fixtures are on Ckts N-2 and N-10 according to the panel and circuit designation on Lighting Plan. Individual fixtures on Lighting Plan are on Ckts 4, 2, and 10. Lights are on Ckts 4 and 10 on panel schedule. Please clarify.
2. There are 2 receptacles without a circuit designation, north side.
3. Receptacles on Ckt N-1, N-3, and N-5 according to the panel and circuit designation on Electrical Plan. N-1 is a spare. Identify which receptacles are to gon on which circuit.
4. Identify panel and circuit on plans for AC.
5. It appears that total for Phase B on panel schedule is 4910, not 3910.
6. It appears that total for Phase C on panel schedule is 5810, not 5370. Correct for high leg as well. Check all totals.
7. Show location of panel N on plans.
8. The #6 GND between the new disconnect and the gutter consists of a redundant path to ground. Pls remove.
9. Panel A appears to be powered from both sides of the line diagram. Pls clarify.
10. The #2 GND between the termination can and the CT can consists of a redundant path to ground. Pls remove.