Permit Number: T04CM04581
Parcel: 12105013B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04581
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2004 JIM EGAN FIRE REVIEW Approved
10/14/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/14/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
10/14/2004 ROBERT SHERRY WATER REVIEW Approved
10/14/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
10/14/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/14/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM04581 DENIED 10/14/04

1. Add new lighting fixtures to new lighting fixture schedule, and provide cut sheets.
2. Load on Ckt 21, 23 is about 9A. This is well below the 33 FLA of the new AC unit.
3. Ckts 22 and 24 would carry 33 A each, well above their 20 A rating.
4. Provide a circuit for the rooftop receptacle.
10/27/2004 TACHONG1 WWM REVIEW Needs Review
10/27/2004 TACHONG1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/27/2004 TAMI ACHONG OUT TO CUSTOMER Completed