Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04581
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/14/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/14/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/14/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/14/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/14/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 10/14/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/14/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM04581 DENIED 10/14/04 1. Add new lighting fixtures to new lighting fixture schedule, and provide cut sheets. 2. Load on Ckt 21, 23 is about 9A. This is well below the 33 FLA of the new AC unit. 3. Ckts 22 and 24 would carry 33 A each, well above their 20 A rating. 4. Provide a circuit for the rooftop receptacle. |
| 10/27/2004 | TACHONG1 | WWM | REVIEW | Needs Review | |
| 10/27/2004 | TACHONG1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/27/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |