Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM04543
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/01/2005 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 02/02/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/02/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | by dwilliams |
| 02/03/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM04543 DENIED 2/2/05 1. Sheet A1 documents booth panel at 120/240V. Electrical drawings provide 120/208 at Panel A schedule, and in 2 places on line diagram. Please coordinate and clarify. 2. CB protecting feeder to lighting disconnect is 200/2. This is a 20A CB on the panel schedule. 3. Please provide TEP available fault current, or annotate an instruction for the Contractor to do so, along with a note that all equipment shall be braced for the AFC. 4. Please run a Grounding Electrode Conductor from the lighting disconnect to the Grounding electrode established at the booth. Reference NEC 250.32 (A). |
| 03/03/2005 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/09/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |