Permit Number: T04CM04543
Parcel: 140420600

Address:
6840 S TUCSON BL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM04543
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2005 PATRICIA GEHLEN ZONING REVIEW Approved
02/02/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/02/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved by dwilliams
02/03/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM04543 DENIED 2/2/05
1. Sheet A1 documents booth panel at 120/240V. Electrical drawings provide 120/208 at Panel A schedule, and in 2 places on line diagram. Please coordinate and clarify.
2. CB protecting feeder to lighting disconnect is 200/2. This is a 20A CB on the panel schedule.
3. Please provide TEP available fault current, or annotate an instruction for the Contractor to do so, along with a note that all equipment shall be braced for the AFC.
4. Please run a Grounding Electrode Conductor from the lighting disconnect to the Grounding electrode established at the booth. Reference NEC 250.32 (A).
03/03/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/09/2005 TAMI ACHONG OUT TO CUSTOMER Completed