Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04538
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/12/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/12/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a water pressure calculation to show how the water piping was sized. |
| 10/12/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/12/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/12/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM04538 DENIED 10/11/04 1. Permit application and system addressing indicates this as 3023 E Pima St. Address on the meter is 3921 E Pima. Please coordinate and clarify. 2. Specify the overcurrent protective device for the Panel P feeder. 3. Provide fault calculations for new Panel P. Note that the fault calculations provided use a "c" value for for copper conductors for the service entrance conductor, whereas that conductor is called out as Aluminum on the line diagram. The fault calculations provided use 3 conductors in parallel for the service entrance conductors, whereas the line diagram indicates 4 parallel sets. Same for Fault #2. Check distances, "c" values, and number of conductors and resubmit. |
| 10/12/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/19/2004 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
| 10/19/2004 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 10/19/2004 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review |