Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM04536
Parcel: 12209003A

Address:
3925 E PIMA ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04536
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2004 JIM EGAN FIRE REVIEW Approved
10/12/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a water pressure calculation to show how the water piping was sized.
10/12/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/12/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM04536 DENIED 10/11/04
1. Permit application and system addressing indicates this as 3025 E Pima St. Address on the meter is 3919 E Pima. Please coordinate and clarify.
2. Specify the overcurrent protective device for the Panel R feeder.
3. Provide fault calculations for new Panel R. Note that the fault calculations provided use a "c" value for for copper conductors for the service entrance conductor, whereas that conductor is called out as Aluminum on the line diagram. The fault calculations provided use 3 conductors in parallel for the service entrance conductors, whereas the line diagram indicates 4 parallel sets. Same for Fault #2. Check distances, "c" values, and number of conductors and resubmit.
10/12/2004 ROBERT SHERRY WATER REVIEW Approved
10/19/2004 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review
10/19/2004 CAGUILA1 WWM REVIEW Needs Review
10/19/2004 CAGUILA1 ZONING REVIEW Needs Review
10/19/2004 CAGUILA1 ENGINEERING REVIEW Needs Review