Permit Number: T04CM04534
Parcel: 13819045A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM04534
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2004 Daniel Castro ZONING REVIEW Denied Building plans may not be approved until the site plan has been approved by all sections and the building plans have been approved by Building Review.
12/01/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. The Pima Department of Environmental Quality must approve the design of the private sewer collection system prior to a review by Development Services of the City of Tucson. Provide plans stamped by PCDEQ.
2. Revise the size of the rain water leader beginning at L-12 to comply with the sizing shown in Table D-2 (1/8" Slope), UPC 1994. The roof drain and overflow (located over room 134) drain 2811 square feet of roof. If the pipe has a slope of 1/8"/foot, a 4" pipe can only handle 2506 square feet of roof.
3. Revise the sleeve for the underslab gas piping in room 109 to provide a vent to the outside. Show how the sleeve is physically configured to meet the intent of the plumbing code. Reference Section 1211.3 (exception), UPC 1994, as modified by the State of Arizona.
4. The 3" waste line shown on detail 1/P202 is carrying 36 fixture units; the maximum capacity of a horizontal 3" waste line is 35 fixture units. Reference Table 7-5, UPC 1994.
12/02/2004 Christy Foreman BUILDING-COMMERCIAL REVIEW Approved CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 12-03-04
ACTIVITY NUMBER: T04CM04534
PROJECT NAME: SAN MIGUEL CATHOLIC HIGH SCHOOL ADMINISTRATION / CLASSROOM BUILDING
PROJECT ADDRESS: 212 W. MEDINA, BLDG. 1
ARCHITECT / ENGINEER: KIM FERRANTI, ABA ARCHITECTS
PROJECT REVIEWER: CHRISTY FOREMAN



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

12-6-04
Stuctural Engineer faxed the additional structural calculation required, therefore I am able to approve.
1) CLARIFY F7 FOOTING CALCULATIONS. - APPROPRIATE DESIGNATIONS NEED TO BE SHOWN ON STRUCTURAL CALCULATIONS AND DRAWINGS.
12/02/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/02/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
12/10/2004 DOUG WILLIAMS ENGINEERING REVIEW Denied Building plans may not be approved until the site plan has been approved by all sections and the building plans have been approved by Building Review.