Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04521
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/11/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
10/11/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/11/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
10/12/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
10/12/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CLARIFY MEETING CHAPT. 11 ACCESSIBILITY AND ANSI 117.1 STANDARDS CODE REQUIREMENTS OR EVALUTION THAT 20% COST OF CONSTRUCTION IS SPENT ON MEETING THE REQUIREMENTS. |
10/12/2004 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | T04CM04521 DENIED 10/11/04 1. It appears that Ckt S-8, with (10) 128 VA existing lighting fixtures and new exterior, emergency, and exit lights, should be counted as having considerably more than 250 VA. Please clarify. 2. Specify the overcurrent protective device for the Panel S feeder. 3. Note that it should not be necessary to provide fault calculations at existing Panel S, considering that this panel and its service are not to be upgraded or relocated. |
10/19/2004 | CAGUILA1 | WWM | REVIEW | Needs Review | |
10/19/2004 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
10/19/2004 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review |