Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM04521
Parcel: 12209003A

Address:
3929 E PIMA ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04521
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2004 ROBERT SHERRY WATER REVIEW Approved
10/11/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/11/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/12/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CLARIFY MEETING CHAPT. 11 ACCESSIBILITY AND ANSI 117.1 STANDARDS CODE REQUIREMENTS OR EVALUTION THAT 20% COST OF CONSTRUCTION IS SPENT ON MEETING THE REQUIREMENTS.
10/12/2004 JIM EGAN FIRE REVIEW Approved
10/12/2004 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review T04CM04521 DENIED 10/11/04
1. It appears that Ckt S-8, with (10) 128 VA existing lighting fixtures and new exterior, emergency, and exit lights, should be counted as having considerably more than 250 VA. Please clarify.
2. Specify the overcurrent protective device for the Panel S feeder.
3. Note that it should not be necessary to provide fault calculations at existing Panel S, considering that this panel and its service are not to be upgraded or relocated.
10/19/2004 CAGUILA1 WWM REVIEW Needs Review
10/19/2004 CAGUILA1 ZONING REVIEW Needs Review
10/19/2004 CAGUILA1 ENGINEERING REVIEW Needs Review