Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T04CM04519
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/14/2004 | Jim Egan | FIRE | REVIEW | Denied | See Site Comments. |
| 10/19/2004 | Robert Suba | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.Provide electrical plan for modular building. 2.See attached list of electrical review requirements.3.All plans to be min. 12 font print. |
| 10/22/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Increase the minimum size of the fonts to 10 points. 2. Revise the site drawing to show the location of the water well and clarify the keynotes shown for the water line. Reference Section 103.2.3, UPC 1994. 3. Revise the site drawing to show the slope of the building drain and the required cleanouts. Reference Section 103.2.3, UPC 1994. 4. Provide the rim elevation of the next upstream and the next downstream sanitary manholes and the first floor elevation. Determine the need for a backwater valve per Section 710.1, UPC 1994. 5. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC 1994. |
| 10/22/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 10/22/2004 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 10/25/2004 | David Rivera | ZONING | REVIEW | Denied | Site plan approval required. |
| 10/26/2004 | Paul Machado | ENGINEERING | REVIEW | Denied | Approved site plan required. |
| 11/15/2004 | Gerry Koziol | WWM | REVIEW | Denied | 1: Trade service building 2: need to show location/method of connection to public sewer. 3: needs par/non-par wastewater evaluation-5th floor. |
| 11/16/2004 | SREEVES1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | plan check stopped due to NSF |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/19/2005 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 07/19/2005 | SUE REEVES | REJECT SHELF | Completed |