Permit Number - T04CM04518
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2005 JIM EGAN FIRE REVIEW Denied 1. Fire hydrant required. Submit approved COT Water Plan.
2. Inadequate exterior openings per 2003 IBC Sec. 903.2.10.
07/21/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the energy code compliance calculations using the current code and show that the building meets the code requirements. Reference Section 101.2, International Energy Conservation Code 2000.
2. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference Section 803.2.8, IECC 2000.
3. Specify the type and size of the flues for the unit heaters and show how the unit heaters are to be mounted to the structure.
07/21/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2003, for business occupancy.
2. Comment not addressed. Revise the site drawing to show the location and size of the water meter and the size of the reduced pressure backflow preventer assembly. Reference Section 103.2.3, UPC 1994.
3. Comment not addressed. Revise the site drawing to show the slope of the building drain and the required cleanouts. Reference Section 103.2.3, UPC 1994.
4. Comment not addressed. Provide the rim elevation of the next upstream and the next downstream sanitary manholes and the first floor elevation. Determine the need for a backwater valve per Section 710.1, UPC 1994.
5. Comment not addressed. Provide material standards for all plumbing fixtures being provided by others. Justify rating the two sinks as "bar sinks". (Note: the minimum waste size for a commercial bar sink is 2".) Revise the plumbing fixture schedule as required, using the fixture unit values shown in Tables 6-3 and 7-3, UPC 1994. Reference Section 703.1, UPC 1994.
6. Clarify the specifications of the water heater; the model number represents a dual element unit wired for 240 volts and 4500 watts and not as shown on the water heater schedule. Reference Section 103.2.3, UPC 1994.
7. Include all of the water fixtures (i.e. hose bibbs) and all of the water requirements of the HVAC equipment (i.e. 4 evaporative coolers, not just one) when calculating the total demand and determining pipe sizes. Reference Section 610.1, UPC 1994.
8. Complete the provided water calculations to show the design pressure drop for the water supply piping system. Note: the lift portion of the calculations is for the elevation difference between the meter and the highest water outlet (e.g. the evaporative coolers). Use the method shown in Appendix A to size the branch piping as well as the main water supply. Reference Section 610.5, UPC 1994.
9. The fixture connection sizes called out for the flush valve will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference Section A 6.1, UPC 1994 and IAPMO IS 3-93, Section 610.0.
10. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference Section 707.4, UPC 1994.
11. Revise the routing of the building drain as necessary to comply with the requirements of Section 313.3, UPC 1994.
12. Resize the natural gas piping per Section 1217.0, UPC 1994 with AZ State amendments.
07/26/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.Plans need to be ledgible to be able to reduce to microfish and still be clear. 2. Provide fault current calculations and equipment to be rated accordingly.
08/10/2005 GERRY KOZIOL WWM REVIEW Denied 1: Trade service building 2:fronts 12" public sewer/ needs to connect to a M.H. new or exsist. 3: needs par/non-par wastewater evaluation-5th floor.
08/12/2005 PAUL MACHADO ENGINEERING REVIEW Approved
08/30/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS


8/30/05

1) The allowable lateral pressure per the I BC is 100 psf. not 150 psf as shown
on calcs. Rectify!
2) Sheet 50 of calcs, shows a design for up-lift. Specify where the values shown
were obtained, also the value for the lateral reaction.
3) Floor plan shows a loft, but there is no no structural framing details to show
any signs of a loft.
4) If there is a loft show some stairs. Provide construction details of stairs and
engineering calcs.
5) Bathrooms shall comply to ADA requirements, provide complete details and
dimensioning.
6) Automatic sprinklers are required.
7) Specify use of building. Provide complete code review check-list.
8) Show all exit signs.
9) Sheet a2 in general note 1, specifies use of IRC, correct to read IBC instead.
10) Calcs, include for dead loads mechanical equipment and automatic sprinklers
if supported on roof.
09/09/2005 DAVID RIVERA ZONING REVIEW Denied 09/09/05

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. Zoning has reviewed the building plans but cannot approve them at this time. Zoning will re-review and approve the building plans on the next submittal providing the stamped and approved site plans are included with the building plan package.

2. Two copies of the approved and stamped site plan, landscape and NPPO plans must be included with building plans.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site and landscape plans.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/12/2005 GBONILL1 OUT TO CUSTOMER Completed
09/12/2005 SUE REEVES REJECT SHELF Completed