Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM04518
Parcel: 141030250

Address:
6473 S WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T04CM04518
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2004 Jim Egan FIRE REVIEW Denied 1. Fire hydrant required.
2. Submit correct code review checklist. Verify B-Occupancy Classification.
10/19/2004 Robert Suba ELECTRICAL-COMMERCIAL REVIEW Denied 1.Sheet E-1 is not clear (poor reproduction) also min. font size is 12. 2.Clarify comment at service diagram regarding available fault current shall be greater or equal to? ( I'm thinking you wanted to say "less than or equal to" ?
10/21/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Increase the minimum size of the fonts to 10 points.
2. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2003, for business occupancy.
3. Provide water supply and waste & vent schematics. Reference Section 103.2.3, UPC 1994.
4. Revise the site drawing to show the location and size of the water meter and the size of the reduced pressure backflow preventer assembly. Reference Section 103.2.3, UPC 1994.
5. Revise the site drawing to show the slope of the building drain and the required cleanouts. Reference Section 103.2.3, UPC 1994.
6. Provide the rim elevation of the next upstream and the next downstream sanitary manholes and the first floor elevation. Determine the need for a backwater valve per Section 710.1, UPC 1994.
7. Revise the plumbing fixture schedule using the fixture unit values shown in Tables 6-3 and 7-3, UPC 1994. Reference Section 703.1, UPC 1994.
8. Provide material standards for all plumbing fixtures being provided by others. Reference Section 103.2.3, UPC 1994.
9. Specify the type, capacity and efficiency of the water heater and provide a detail showing how the water heater is to be piped. Reference Section 103.2.3, UPC 1994.
10. All storage-type water heaters require a listed expansion tank. Please show expansion tanks on plans. Reference Section 608.3, UPC 1994 with AZ State amendments.
11. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping along with ½" insulation on the first eight feet of supply and discharge piping. Reference Sections 804.4 and 804.5, IECC 2000.
12. Include all fixtures and the water requirements of the HVAC equipment when calculating the total demand and determining pipe sizes. Reference Section 610.1, UPC 1994.
13. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC 1994.
14. Limit the water velocity to less than 8 fps for the PVC and Copper piping. Reference Section A 6.1, UPC 1994; IAPMO IS 3-93, Section 610.0; and IAPMO IS 8-92, Section 610.1.
15. Clarify which piping is to be above grade and which is to be below grade. Show piping to all fixtures and to the HVAC equipment. Reference Section 103.2.3, UPC 1994.
16. Show the natural gas meter and piping on the drawing. Provide the natural gas pipe sizing calculations. Include gas pressures and developed pipe lengths on plans. Reference Section 1217.0, UPC 1994 with AZ State amendments.
10/21/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Increase the minimum size of the fonts to 10 points.
2. Provide energy code compliance calculations. Reference Section 101.2, International Energy Conservation Code 2000.
3. Provide sufficient heat for the shop area to maintain a minimum temperature of 68°F on a design heating day (32°F). Reference Section 309.1, IMC 2000.
4. Provide calculations demonstrating adequate ventilation in the office areas. Reference Section 401, IMC 2000.
5. Ventilation for restrooms in public spaces requires a minimum of 75 CFM of mechanical exhaust per water closet or urinal. Reference Sections 403.2.1 (3) and 403.3, IMC 2000.
6. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference Section 803.2.8, IECC 2000.
7. Show the size, routing, and termination of the condensate drain. Reference Section 307.2, IMC 2000 and Section 807.2, UPC 1994.
8. Show the size, routing, and termination of the drains from the evaporative coolers. Reference Section 106.3.1, IMC 2000.
10/21/2004 ROBERT SHERRY WATER REVIEW Approved
10/25/2004 David Rivera ZONING REVIEW Denied Site plan approval required.
10/26/2004 Paul Machado ENGINEERING REVIEW Denied Approved site plan required.
11/15/2004 Gerry Koziol WWM REVIEW Denied 1: Trade service building 2: need to show location/method of connection to public sewer. 3: needs par/non-par wastewater evaluation-5th floor.
11/16/2004 SREEVES1 BUILDING-COMMERCIAL REVIEW Needs Review plan check stopped due to NSF

Final Status

Task End Date Reviewer's Name Type of Review Description
02/18/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
02/18/2005 SUE REEVES REJECT SHELF Completed