Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04456
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/07/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/07/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show that the access to the water heater conforms to Section 511.2, UPC 1994. |
| 10/07/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/07/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/07/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide ventilation calculations. Reference Section 403.3, IMC 2000. |
| 10/08/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) ANSI A117.1 WATER CLOSET CLEARANCE 604.3.1, MANEUVERING CLEARANCE AT DOORS SECTION 404 ANSI A117.1. 2) CLARIFY WALLS AND OPENINGS TO BE REMOVED ARE NON-BEARING OR BEARING PROVIDE STRUCTURAL CALCS. 3) PROVIDE INTERIOR PARTITION WALL SECTION. 4) CLARIFY NOTATION OF TEMPERED GLASS. |
| 10/21/2004 | TACHONG1 | WWM | REVIEW | Needs Review | |
| 10/21/2004 | TACHONG1 | ZONING | REVIEW | Needs Review | |
| 10/21/2004 | TACHONG1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/21/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |