Permit Number: T04CM04456
Parcel: 12909146C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04456
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2004 JIM EGAN FIRE REVIEW Approved
10/07/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show that the access to the water heater conforms to Section 511.2, UPC 1994.
10/07/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
10/07/2004 ROBERT SHERRY WATER REVIEW Approved
10/07/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide ventilation calculations. Reference Section 403.3, IMC 2000.
10/08/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) ANSI A117.1 WATER CLOSET CLEARANCE 604.3.1, MANEUVERING CLEARANCE AT DOORS SECTION 404 ANSI A117.1.
2) CLARIFY WALLS AND OPENINGS TO BE REMOVED ARE NON-BEARING OR BEARING PROVIDE STRUCTURAL CALCS.
3) PROVIDE INTERIOR PARTITION WALL SECTION.
4) CLARIFY NOTATION OF TEMPERED GLASS.
10/21/2004 TACHONG1 WWM REVIEW Needs Review
10/21/2004 TACHONG1 ZONING REVIEW Needs Review
10/21/2004 TACHONG1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/21/2004 TAMI ACHONG OUT TO CUSTOMER Completed