Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM04443
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/06/2005 | Robert Suba | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/18/2005 | Doug Laakso | BUILDING-COMMERCIAL | REVIEW | Denied | .. T04CM04443-1 .. 529 N FORGEUS AVENUE .. DGL .. 2000 IBC .. .. 2nd REVIEW .. 1/20/05 S1. Petition of Appeal to Building Official regarding design as two duplexes with two-hour fire wall separating the duplexes. S2. Petition of Appeal to Building Official regarding one bedroom apartment to the east of garage. S3. Lot combo required . If the above are approved many of the 1st Review Comments will be addressed . Review completed until S1, S2, and S3 reviewed and resolved. S1. Building permits required to : 1. Convert one -story storage space to the east to a dwelling unit. 2. Convert the 4-car garage to a two-car garage with storage. 3. Convert hobby room/s on second floor over garage to apartment/s. per City of Tucson Records for this address. S2. Provide corrected Code Review Checklist that accurately reflects occupancy/ies , mixed occupancies , separation requirements , special detailed requirements based on use and occupancy , allowable area calculation. S3. Provide site plan with property lines clearly shown , describing and locating building/s on site plan. S4. Clearly indicate location , type of fire wall/s and hourly fire-ratings of walls and floors providing separation required by the IBC . S5. Delete door frame from 5/A2 and show details at sill and head of this opening including connections to existing wall at jambs , sill and head. S6. Cut nails are not acceptable in commercial construction due to no definite value as a connector , please specify fasteners with tested and listed values. S7. Provide typical furr-out detail. S8. Clarify interior finishes compliance with IBC Section 8 and Table 803.4. S9. Show location of smoke detectors at unit to the east. S10. Show on drawings conformance with accessiblity requirements of IBC and ANSI A117.1-98ed. S11. Clarify opening protection conforms to IBC Section 7. S12. Show fire-resistant joint systems comply with IBC Section 7. S13. Show connection details for wrought iron screen on 2nd floor patio. S14. Show fire assembly penetrations conform to IBC Section 7. S15. Clarify emergency egress from 2nd floor bedroom to east. S16. Provide structural calculations to show roof structure capable of supporting units on roof as well as required dead and live loads. Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/21/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 01/21/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |