Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM04442
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/19/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
10/19/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide ventilation air for the office. Transfer air is not allowed as a source of ventilation for an office. Reference Sections 403.2.2 and 403.3, IMC 2000. |
10/19/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the water velocity in the copper piping at the RPBP and within 10 feet from the slab does not exceed 8 feet per second.Reference Section 610.0, IAPMO IS 3-93 and Section A6.1, UPC 1994. 2. Clarify the design of the combustion air intakes to show how the required free area is provided. Show the combustion air calculations on the drawing. Reference Section 507.4, UPC 1994. |