Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T04CM04442
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/12/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. City of Tucson Ordinance 1802 requires a reduced pressure backflow preventer to be located immediately after the water meter. A Wilkins 950XL is a double check valve and is not approved for this use. 2. Clarify how the piping arrangement in detail 2/P-2 is supposed to work 3. Resize the reduced pressure backflow preventor to comply to Section 610.2, UPC 1994. 4. Revise the combustion air calculations per Chapter 5 of the Arizona State Plumbing Code (Table A, footnote 3). The free area of the screen or louver shall be used to calculate the size of the required opening. Reference Section 507.4, UPC 1994. |
| 10/12/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the laundry room and office comply with Section 309.1, IMC 2000. 2. Provide ventilation air for the office. Reference Sections 403.2.2 and 403.3, IMC 2000. |
| 10/13/2004 | TACHONG1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/13/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |