Permit Number: T04CM04442
Parcel: 13805045H

Address:
6416 S 12TH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04442
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2004 JIM EGAN FIRE REVIEW Approved
10/06/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
10/06/2004 JIM TATE ENGINEERING REVIEW Approved
10/08/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
10/08/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied DENIED 10/08/04
1. Please note that the City now enforces the 2002 NEC, effective July 1. Pls change "1999" to "2002" on Sheet E-2 Note 1, and anywhere lese where the superceded Code is referenced.
2. New service is drawn as overhead, but keynotes indicate conduit. Please clarify.
3. Please note that overhead service is not acceptable for new services unless the existing service (being replaced) is already overhead.
4. If 600 MCM is an option for the new service entrance conductors, then the Grounding /electrode Conductor shall not be smaller than 2/0 per NEC Table 250-66.
10/11/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
10/11/2004 GERRY KOZIOL WWM REVIEW Approved
10/11/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
10/11/2004 ROBERT SHERRY WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/11/2004 TAMI ACHONG OUT TO CUSTOMER Completed