Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM04427 DENIED 10/08/2004
1. Allocated 1/2 of track lighting for each circuit indicated, typical. Ckt LV-2, with 24 LF of track lighting allocated, would have (24) (75) (1.25) = 2250 VA at continuous load.
2. Ckt LV-4, with 24 LF of track lighting allocated, would have (24) (75) (1.25) = 2250 VA at continuous load.
3. Ckt LV-6, with 16 LF of track lighting allocated, and (5) fixtures F, would have (16) (75) + (5) (75) = 1968 VA at continuous load.
4. Ckt LV-8, with 16 LF of track lighting allocated, would have (16) (75) (1.25) = 1500 VA at continuous load.
5. LV-25 powers the WH on Electrical Plan. This is a space on the panel schedule. Please clarify.
6. Fault #2 lists 200' to Panel HV. Calculations use 330'. I measure about 130' from the newly submitted site diagram. Pls clarify.
10/13/2004 EGRANT1 WWM REVIEW Needs Review