Permit Number: T04CM04427
Parcel: 12801005H

Review Status: Completed

Review Details: OTHER

Permit Number - T04CM04427
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/07/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM04427 DENIED 10/07/04
1. Ckts LV-2, LV-4, and LV-6, with track lighting, shall be counted as no less than 75 VA per linear foot.
2. Account for load on panel schedule LV-22, LV-24, LV-25.
3. Suggest to apply a 6 amp fuse to the FCU units, unless manufacturer recommends otherwise.
4. Show electrical service location on scaled drawing.
5. Provide AFC and fault calculations.
10/08/2004 LLESNY1 WWM REVIEW Needs Review