Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/07/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
10/07/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM04427 DENIED 10/07/04 1. Ckts LV-2, LV-4, and LV-6, with track lighting, shall be counted as no less than 75 VA per linear foot. 2. Account for load on panel schedule LV-22, LV-24, LV-25. 3. Suggest to apply a 6 amp fuse to the FCU units, unless manufacturer recommends otherwise. 4. Show electrical service location on scaled drawing. 5. Provide AFC and fault calculations. |