Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM04405
Parcel: 12701005D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04405
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2004 JIM EGAN FIRE REVIEW Approved
10/04/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/04/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
10/04/2004 ROBERT SHERRY WATER REVIEW Approved
10/04/2004 PATRICIA GEHLEN ZONING REVIEW Approved
10/04/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/05/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
10/05/2004 GERRY KOZIOL WWM REVIEW Completed
10/05/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/05/2004 LISA LESNY OUT TO CUSTOMER Completed