Permit Number: T04CM04402
Parcel: 21248069E

Review Status: Completed

Review Details: OTHER

Permit Number - T04CM04402
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2004 Doug Laakso BUILDING-COMMERCIAL REVIEW Denied .. T04CM04402 .. 4401 S TUCSON ESTATES PARKWAY .. DGL ..
.. 1ST REVIEW .. 11/23/04

S1. Dimensionally new locate cooling towers and new mechanical unit on the roof from two adjacent walls.
S2. Provide complete stair details ref 6/S2 and 1/S1 (Where are Architectural Drawings?) :
1. Rise and run
2. Handrails w/ details.
3. Guards if height of stair exceeds 30".
S3. Special inspection required for :
1. Field welding.
2. Epoxy anchors.
3. Expansion anchors.
S4. Provide 2 sets of approved shop drawings for :
1. Cooling towers.
2. Mechanical unit on the roof.
3. Unistrut pipe supports.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111

Final Status

Task End Date Reviewer's Name Type of Review Description
11/30/2004 LISA LESNY OUT TO CUSTOMER Completed
11/30/2004 SUE REEVES REJECT SHELF Completed