Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T04CM04402
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/22/2004 | Doug Laakso | BUILDING-COMMERCIAL | REVIEW | Denied | .. T04CM04402 .. 4401 S TUCSON ESTATES PARKWAY .. DGL .. .. 1ST REVIEW .. 11/23/04 S1. Dimensionally new locate cooling towers and new mechanical unit on the roof from two adjacent walls. S2. Provide complete stair details ref 6/S2 and 1/S1 (Where are Architectural Drawings?) : 1. Rise and run 2. Handrails w/ details. 3. Guards if height of stair exceeds 30". S3. Special inspection required for : 1. Field welding. 2. Epoxy anchors. 3. Expansion anchors. S4. Provide 2 sets of approved shop drawings for : 1. Cooling towers. 2. Mechanical unit on the roof. 3. Unistrut pipe supports. Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/30/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 11/30/2004 | SUE REEVES | REJECT SHELF | Completed |