Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM04397
Parcel: 136261300

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04397
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the fixture connection schedule (floor sinks) to coordinate with the plumbing floor plan.
2. Revise the water fixture units for the beverage/ice dispenser in the fixture connection schedule from 2 units to 4 units. Reference Table 6-3, UPC 1994.
3. Termination of the excess pressure relief from the water heater over a service sink is not approved location. Reference Section 608.5, UPC 1994.
4. Provide a complete riser diagram of the water piping.
5. Provide material standards for all plumbing fixtures being provided by others. Reference Section 103.2.3, UPC 1994
10/11/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the existing exhaust fan in the existing restroom complies with the airflow requirements of Section 403.3, IMC 2000.
2. Clarify the amount of outside air being provided by HP-1; the ventilation calculations call for 400 CFM but the unit schedule calls for 500 CFM.
3. Show how the outside air introduced into the tenant space compared to the total exhaust from the space complies with Sections 403.1 and 508.1, IMC 2000.
4. Show how the exhaust airflow for the grease hood meets the requirements of Section 507.13.2, IMC 2000.
5. Provide dimensions, installed weight, and construction information for the grease hood. Reference Section 106.3.1, IMC 2000.
6. Provide structural calculations to show that the method of attaching the grease hood to the building structure (detail 5/A2) meets the requirements of Section 507.6, IMC 2000.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/13/2004 TAMI ACHONG OUT TO CUSTOMER Completed
10/13/2004 ANGIE SHOFFSTALL REJECT SHELF Completed