Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04397
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/11/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the fixture connection schedule (floor sinks) to coordinate with the plumbing floor plan. 2. Revise the water fixture units for the beverage/ice dispenser in the fixture connection schedule from 2 units to 4 units. Reference Table 6-3, UPC 1994. 3. Termination of the excess pressure relief from the water heater over a service sink is not approved location. Reference Section 608.5, UPC 1994. 4. Provide a complete riser diagram of the water piping. 5. Provide material standards for all plumbing fixtures being provided by others. Reference Section 103.2.3, UPC 1994 |
10/11/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the existing exhaust fan in the existing restroom complies with the airflow requirements of Section 403.3, IMC 2000. 2. Clarify the amount of outside air being provided by HP-1; the ventilation calculations call for 400 CFM but the unit schedule calls for 500 CFM. 3. Show how the outside air introduced into the tenant space compared to the total exhaust from the space complies with Sections 403.1 and 508.1, IMC 2000. 4. Show how the exhaust airflow for the grease hood meets the requirements of Section 507.13.2, IMC 2000. 5. Provide dimensions, installed weight, and construction information for the grease hood. Reference Section 106.3.1, IMC 2000. 6. Provide structural calculations to show that the method of attaching the grease hood to the building structure (detail 5/A2) meets the requirements of Section 507.6, IMC 2000. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/13/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
10/13/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |