Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM04397
Parcel: 136261300

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04397
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2004 JIM EGAN FIRE REVIEW Approved
10/04/2004 ROBERT SHERRY WATER REVIEW Approved
10/04/2004 PATRICIA GEHLEN ZONING REVIEW Approved
10/04/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/05/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
10/07/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
10/07/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM04397 DENIED 10/05/04
1. Circuits 12A-21,23 are shown twice on the plans, once for a 2-P disconnect, and powering receptacles in another place. Please clarify. (One may be the new Insta-Hot, which should read "12A-28,30".
2. Provide a disconnect for the hardwired Freezer on Ckt 12A-24,26, or justify otherwise. NEC 422.31 (B).
3. Provide overload protection for EF-1, or justify otherwise.
10/07/2004 GERRY KOZIOL WWM REVIEW Approved
10/07/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review