Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04397
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/04/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
10/04/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/04/2004 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
10/04/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
10/05/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/07/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
10/07/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM04397 DENIED 10/05/04 1. Circuits 12A-21,23 are shown twice on the plans, once for a 2-P disconnect, and powering receptacles in another place. Please clarify. (One may be the new Insta-Hot, which should read "12A-28,30". 2. Provide a disconnect for the hardwired Freezer on Ckt 12A-24,26, or justify otherwise. NEC 422.31 (B). 3. Provide overload protection for EF-1, or justify otherwise. |
10/07/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
10/07/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review |