Permit Number: T04CM04388
Parcel: 130100600

Address:
3173 E 24TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T04CM04388
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2004 Gerry Koziol WWM REVIEW Approved
12/07/2004 Bruce Stevens BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS PROJECT #T04CM04388
12/07/2004 3173 E. 24th St.

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.
SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical. All code references are to the 2003 International Residential Code, 2000 International Energy Conservation Code, and Arizona State Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
GENERAL REQUIREMENTS:
1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia & (1) blue line shall be returned along with all redline prints. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
FLOOR PLANS:
1. Locate and identify brace wall types and locations along with the appropriate nailing schedule.
2. Identify ceiling heights in all areas on floor plan. If sloped ceiling, note average height.
3. All exterior doors require a landing or floor at the exterior. Landings must be at least as wide as the doors they serve and 36" in the direction of travel per R311.4.3.

STRUCTURAL PLANS:
1. Specify design criteria on plans. Provide values for roof dead load and live load that were used to calculate rafter size.
2. Provide a complete roof framing plan. Detail shows prefab trusses, whereas framing plan shows 2X8 rafters. Please show only the one that is correct.
3. If prefab trusses are used, provide manufacturer's calculations and data. Truss calculations must be signed, dated and wet-sealed by an engineer who is registered in Arizona. Truss calculations shall be cross-referenced to the floor plans. The engineer of record shall review and "SHOP DRAWING" stamp approval on truss calculations.
4. If 2X8 rafters 24"oc is used, they will not be adequate to support the roof load. You could use either 2X10 @ 24"oc or 2X8 @ 16"oc to meet the span requirement.
5. Detail rafter connection at intersection of existing construction to new construction.
6. Provide brace wall details and notes for exterior frame walls and main cross-stud partitions, or use fully braced, per R602.10.3. A minimum panel width of 48" is required to effectively brace the partition. See table R602.10.3, category "C". If bracing does not comply, provide a lateral analysis or alternate design to be reviewed by the plan examiner. Wind forces for single story residences shall use 90 MPH, exposure "B". Two story residences or areas of higher wind shall use exposure "C".
7. Detail all brace wall connections from the foundation to the roof plywood.
SECTIONS - DETAILS - MISC. NOTES:
1. Wood sill plates shall be foundation grade redwood or pressure-treated wood per R320.
PLUMBING PLANS:
1. Note and specify all piping materials.
2. Note on plan compliance with the water conservation requirements. Water closets, 1.6 gallons per flush, sinks and shower heads, 3 gallons per minute.
3. Note on plans that shower and tub / shower combinations that have individual control valves shall be of the pressure balance or thermostatic mixing valve type.
4. The City of Tucson has adopted the 1994 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). All plans must reference this code.
MECHANICAL PLANS:
1. Note on plans: Mechanical shall comply with 2003 IRC chapters 13 - 24.
2. The dwelling must be provided with heating capable of maintaining a room temperature of 68 degrees at a point 3' above the floor per R303.8.
3. Return air shall be sized per IRC sections M1602.2. (gas furnace - 2 sq. in. / 1000 BTU; heat pump / air conditioner - 6 sq. in. / 1000 BTU) (1ton cooling = 12,000 BTU) Provide for the appropriate portion of return air to be drawn from the addition.
ELECTRICAL PLANS:
1. Note on plan that all electrical work shall comply with 2000 IRC chapters 33 - 42.
2. Note the location, type and amperage of the panel. Note the grounding and bonding method. Metallic gas lines must be bonded and shall not be used as grounding method.
3. Provide an exterior outlet at grade level located at both the front and back of the dwelling, per E3801.7. these outlets shall be GFCI protected per E3802.3.
4. A receptacle outlet shall be provided adjacent to the basin in each bathroom, per E3801.6. Bathroom outlets shall be on a separate 20 AMP circuit with no other outlets, per E3603.4.
5. All receptacle outlets in bathrooms, kitchens, unfinished basements, garages or carports, at grade level and within 6' of a wet bar or kitchen sink shall have ground fault circuit interrupting protection. Note on the drawings at each outlet requiring such protection, per E3802.
6. Note that at least one 20 AMP branch circuit shall be installed to serve the laundry room and this circuit shall have no other outlets, per E3603.3 and 3801.8.
7. Where ceiling fans are shown on the plans, provide a note indicating only approved outlet boxes shall be used, per E4001.6.
8. Show locations of smoke detectors per R313. Note that all smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. When ceiling finish materials are removed in existing construction, existing bedrooms shall be in compliance. When ceiling finish materials are not removed, existing bedrooms shall be equipped with battery operated smoke detectors per R313.1.1.
MODEL ENERGY CODE:
1. Provide energy calculations per the 1998 IECC and comply with IRC chapter 11.
2. Call out on the plan the "R" values of insulation, as well as the "U" values of the windows and doors in compliance with the energy calculations provided. The 'R30' insulation you have specified in the ceiling is not possible with 2X8 rafters.
If you have any questions, please contact your assigned plans examiner Bruce Stevens at 791-5550, extension 1174.
NOTE: As of 09/06/04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the Arizona state plumbing code. All model plans shall reference these codes.