Permit Number: T04CM04383
Parcel: 13311010A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM04383
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2005 Raul Palma BUILDING-COMMERCIAL REVIEW Denied 1) Provide bracing as per our phone call. See detail
a/a3 where menu board is hung.
12/22/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. No cut sheet supplied. Provide listing information (on the drawing) for exhaust fan EF-1 that shows the fan is suitable for use as an exhaust fan for a Type I grease hood and complies with Sections 506.3.1, 506.3.3.3, 506.3.8, and 506.3.13, IMC 2000. No cut sheet supplied.
2. No cut sheet provided. Provide information (on the drawing) to show what types of cooking equipment is to be used under the Type I hood. Reference Section 106.3.1, IMC 2000.
3. No cut sheet provided. Provide the weight and construction information for the Type I hood (on the drawing) to show that it complies with the requirements of Section 507, IMC 2000.
4. No cut sheet provided. Show on the drawing that the termination of EF-1 complies with the requirements of Section 506.3.13.3, IMC 2000.
5. No cut sheet provided. Provide the listing information for the makeup air unit on the drawing. Reference Section 301.4, IMC 2000.
6. No cut sheet provided. Provide information (on the drawing) to show that the insulation of the HVAC ductwork complies with the requirements of Section 803.2.8, IECC 2000.
12/22/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the meaning of the entries in the "water fixtures" column of the plumbing fixture schedule. Reference Section 103.2.3, UPC 1994.
2. Coordinate the "water fixture count" and "water demand" tables on sheet P1 with Table 6-3, UPC 1994.
3. Revise the waste "fixture unit tabulation" in the plumbing fixture schedule using the values shown in table 7-3, UPC 1994. Reference Section 703.1, UPC 1994.
4. No cut sheet provided. Provide material standards for the plumbing fixture fittings for the mop sink and for those being provided by others. Reference Section 103.2.3, UPC 1994.
5. No cut sheet provided. Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers or other backflow prevention devices. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994.
6. No cut sheet provided. Provide water pressure and water pipe sizing calculations. Show the pipe sizes on the drawing. Reference Section 610.4, UPC 1994.
7. The "3-compartment sink" is called out as a "4-compartment" sink in the water demand calculations and in "new riser 1". Coordinate the fixture call outs.
8. No cut sheet provided. Provide listing information for the grease trap that shows it is designed for a 2" inlet and outlet. Reference Section 103.2.3, UPC 1994.
9. Comment not addressed. Revise the design of the vent for the grease trap to comply with the requirements of Section 905.2, UPC 1994.
10. Provide a vent for each plumbing fixture. Reference Section 901.0, UPC 1994. Clarify the double venting of the floor sink and the arrangement of the cleanout for the hand sink.
11. Comment not addressed Revise the sizes of the vents as required to comply with Section 904.1, UPC 1994.
12. Comment not addressed. Show that the design of the "cabinet mounted" indirect waste receptor complies with Section 804.1, UPC 1994. Explain the meaning of the note, "new indirect reversed below counter for mounted indirect from soda machine sink, beverage bar".
12/30/2004 Robert Suba ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/25/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
01/25/2005 ANGIE SHOFFSTALL REJECT SHELF Completed