Permit Number: T04CM04383
Parcel: 13311010A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04383
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Needs Review
10/20/2004 LLESNY1 WWM REVIEW Needs Review
10/20/2004 LLESNY1 PLUMBING-COMMERCIAL REVIEW Needs Review
10/20/2004 LLESNY1 WATER REVIEW Needs Review
10/20/2004 LLESNY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review T04CM04383 DENIED 10/18/04
1. Power plan has keynote symbols but no corresponding keynotes. Pls clarify.
2. Provide circuit breaker size for B-3.
3. Provide circuit breaker size for B-5.
4. Electric griddle appears to be on Circuit B-15,17 on power plan. According to the panel schedule this equipment is on a 50A CB on Ckts 13,15 17 which takes up three spaces but only consists of 2 poles. Pls clarify, and recheck loading on these circuits.
5. Amps for Panel B should be 64A.
(22984/(1.73)(208) = 64.
6. Amps for Panel A should be 172 A.
(62234)/(1.73)(208)=172.
7. Date plans were signed by registrant 2/05/04. First comments made 10/06/04. Registrant shall reseal and sign and date to actual date.
10/20/2004 LLESNY1 MECHANICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/20/2004 LISA LESNY OUT TO CUSTOMER Completed