| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/18/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 10/20/2004 | LLESNY1 | WWM | REVIEW | Needs Review | |
| 10/20/2004 | LLESNY1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 10/20/2004 | LLESNY1 | WATER | REVIEW | Needs Review | |
| 10/20/2004 | LLESNY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | T04CM04383 DENIED 10/18/04 1. Power plan has keynote symbols but no corresponding keynotes. Pls clarify. 2. Provide circuit breaker size for B-3. 3. Provide circuit breaker size for B-5. 4. Electric griddle appears to be on Circuit B-15,17 on power plan. According to the panel schedule this equipment is on a 50A CB on Ckts 13,15 17 which takes up three spaces but only consists of 2 poles. Pls clarify, and recheck loading on these circuits. 5. Amps for Panel B should be 64A. (22984/(1.73)(208) = 64. 6. Amps for Panel A should be 172 A. (62234)/(1.73)(208)=172. 7. Date plans were signed by registrant 2/05/04. First comments made 10/06/04. Registrant shall reseal and sign and date to actual date. |
| 10/20/2004 | LLESNY1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/20/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |