Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04383
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/05/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 10/05/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 10/06/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM04383 DENIED 10/6/04 1. Circuit B-14 powers receptacles on power plan. But is listed as a spare on panel schedule. Please clarify. 2. Power plan has keynote symbols but no corresponding keynotes. Pls clarify. 3. Ckt A-22,24 Water Heater needs load on panel schedule. 4. Ckt B-8 is listed twice on the power plan. Pls clarify. 5. Provide circuit breaker size for B-3. 6. Provide circuit breaker size for B-5. 7. Provide conductor size for B-13,15. 8. Provide load on panel schedule for B-12. 9. Provide load on panel schedule for B-26. 10. Provide amps for Panel B. 11. If totals for Phases A, B, and C on Panel A are correct, this panel is overloaded. 12. Show calculation for 80826 KVA for Panel A. 13. Show calculation for 179 KVA for Panel A. 14. Show calculations for new connected load for Panel A. |
| 10/06/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/18/2004 | TACHONG1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 10/18/2004 | TACHONG1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 10/18/2004 | TACHONG1 | WWM | REVIEW | Needs Review | |
| 10/18/2004 | TACHONG1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 10/18/2004 | TACHONG1 | WATER | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/18/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |