Permit Number: T04CM04383
Parcel: 13311010A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04383
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/05/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
10/06/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM04383 DENIED 10/6/04
1. Circuit B-14 powers receptacles on power plan. But is listed as a spare on panel schedule. Please clarify.
2. Power plan has keynote symbols but no corresponding keynotes. Pls clarify.
3. Ckt A-22,24 Water Heater needs load on panel schedule.
4. Ckt B-8 is listed twice on the power plan. Pls clarify.
5. Provide circuit breaker size for B-3.
6. Provide circuit breaker size for B-5.
7. Provide conductor size for B-13,15.
8. Provide load on panel schedule for B-12.
9. Provide load on panel schedule for B-26.
10. Provide amps for Panel B.
11. If totals for Phases A, B, and C on Panel A are correct, this panel is overloaded.
12. Show calculation for 80826 KVA for Panel A.
13. Show calculation for 179 KVA for Panel A.
14. Show calculations for new connected load for Panel A.
10/06/2004 JIM EGAN FIRE REVIEW Approved
10/18/2004 TACHONG1 PLUMBING-COMMERCIAL REVIEW Needs Review
10/18/2004 TACHONG1 BUILDING-COMMERCIAL REVIEW Needs Review
10/18/2004 TACHONG1 WWM REVIEW Needs Review
10/18/2004 TACHONG1 MECHANICAL-COMMERCIAL REVIEW Needs Review
10/18/2004 TACHONG1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/18/2004 TAMI ACHONG OUT TO CUSTOMER Completed