Permit Number: T04CM04349
Parcel: 11450004K

Review Status: Completed

Review Details: REVISION

Permit Number - T04CM04349
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/26/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Regarding the fault calculations, there was no change submitted on the electrical site plan for a new transformer location cited in the Memo from BDA dated 8/5/05. Distance scales out to be about 57'. Assuming 55600A available at the service entrance, and accepting the 25' distance to panels A and B, Electrical Plans Examiner calculates 29,244A available at Panel A and 35,025A available at Panel B, both of which exceed the 22K ratings. Since the 55600A is the value at the TEP transformer it may help to use this distance to reduce the AFC at the service entrance. Panel A appears to be 29' from the service entrance, not 25'. Panel B appears to be 32' from the service entrance, not 25'.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/26/2005 JMORALE1 OUT TO CUSTOMER Completed
08/26/2005 SUE REEVES REJECT SHELF Completed