Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM04349
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/01/2005 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 06/02/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/02/2005 | SREEVES1 | WWM | REVIEW | Approved | |
| 06/09/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The information provided regarding the Jorvet Gas-vac Active Anesthesia Scavenger does not show that the system is Listed or Labeled by an approved testing agency. Reference Appendix F, UPC 1994 as amended by the State of Arizona. |
| 06/09/2005 | EGRANT1 | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 06/09/2005 | EGRANT1 | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 06/09/2005 | EGRANT1 | ENGINEERING | REVIEW | Passed | |
| 06/09/2005 | EGRANT1 | WATER | REVIEW | Passed | |
| 06/23/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Ckt B-14,16 powers F-1. Mechanical M100 Keyed Note 14 calls for a 5KW, 240V 3-phase unit. Electrical calls for a 208V, single phase unit. Pls coordinate with Mechanical and clarify. THIS WAS NOTED ON THE REVIEW OF 1/25/05 AND THE REVIEW OF 4/12/05. 1. Grounding System General Note A instructs the Contractor to augment the grounding electrode system with Items B, C, or E as necessary to insure = 25? to ground. Items B and C address Main Bonding Jumper, which is always required per NEC 250.28. Item E addresses the Grounding Electrode Conductor, which is always required per NEC 250.24. NEED FOR CLARIFICATION WAS NOTED ON THE REVIEW OF 1/25/05 AND THE REVIEW OF 4/12/05. 3. "Please submit catalogue cut sheets for Fixtures M and L1. All exterior fixtures shall comply with the Lighting Ordinance http://www.ci.tucson.az.us/dsd/Codes___Ordinances/Outdoor_Lighting_Code.pdf and be clearly listed for damp or wet locations as appropriate. Exterior Lighting per 2002 IECC 805.5." THIS COMMENT WAS MADE ON THE REVIEW OF 1/25/05 AND THE REVIEW OF 4/12/05. Fixture L1, from the catalogue number on the Lighting Fixture Schedule, appears to be incandescent; if the building was not existing in 1994, the 2000 IECC Section 805.5 would apply. Fixture M fixture cut sheet not included in current submittal; demonstrate fully shielded configuration, as defined by the Lighting Ordinance in effect at the time these plans were generated: "…fixtures shielded or constructed so that no light rays above the horizontal plane, as certified by photometric test report." |