| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2005 | DAVID RIVERA | ZONING | REVIEW | Approv-Cond | |
| 05/12/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/24/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Sheet UT.01 has not been updated to show the location of the reduced pressure backflow preventer or the revised water line size. 2. Clarify the design of the natural gas piping. The gas riser diagram on sheet P601 shows conflicting gas loads and developed lengths for the rooftop units and the pipe sizes on the gas riser diagram do not agree with the piping plan shown on sheet P102. 3. The information provided regarding the Vetroson Active Anesthesia Scavenger does not show that the system and its installation complies with the requirements of NFPA 99, Chapter 4 (1996 edition) or that the unit is even Listed or Labeled. Reference Appendix F, UPC 1994, as amended by the State of Arizona. |
| 05/24/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/26/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | |
| 06/01/2005 | KMEDINA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |