Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM04349
Parcel: 11450004K

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM04349
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied 1) Being that 2 means of egress is required, the corridor is required to be 1-hr fire
protected and doors openings shall be 20 min. All penetrations into corridor
walls shall be protected with fire dampers.
2) All text in calc`s shall be a minimum of 10 point font.
03/31/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The provided calculations do not demonstrate adequate ventilation based on the requirements of Sections 403.3 and 403.3.2, IMC 2000. Revise and resubmit.
2. Show how the recirculation of air from one zone to another (i.e. dissimilar occupancies) complies with the requirements of Section 403.2.1, IMC 2000.
3. The response to Comment #4 stated that the energy recovery unit ERU-1 was to be set to 2055 CFM of exhaust to correspond to the air pressurization summary. Note #3 for the energy recovery unit accessories for the Air Handling Unit Schedule calls for 1550 CFM of exhaust. Please clarify.
4. Show the sizes of the condensate drains. Arizona State law (A.R.S. § 32-145) prevents the contractor from practicing engineering without being registered. The minimum condensate drain size is ¾" and combined condensate drains must be sized for the aggregate condensate flow. Clarify the double condensate drains from the three rooftop units. Reference Sections 307.2 and 307.2.2, IMC 2000 and Section 807.2, UPC 1994.
5. Comment not addressed. Show the size, routing, and termination of the drain from the evaporative cooler. Reference Section 103.2.3, UPC 1994.
6. Clarify the positioning of the oxygen room vents as noted in keynote #7, sheet M100.
03/31/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 1994 Uniform Plumbing Code with Arizona State Amendments. Revise the water fixture unit calculations per Section 610.1, UPC 1994. Please note the definition of "Public or Public Use" in Section 202.0, UPC 1994.
2. Resize the reduced pressure backflow preventor to comply to Section 610.2, UPC 1994. Provide a cut sheet for the specified reduced pressure backflow preventer confirming a pressure drop of 7 psi for the calculated flow. Show the location of the backflow preventer on the drawings.
3. Revise the provided water pressure and water pipe sizing calculations to include the static lift (from the meter to the highest outlet). Reference Section 610.4, UPC 1994.
4. Include the water requirements of the HVAC equipment when calculating the total demand and determining pipe sizes. Reference Section 610.1, UPC 1994. Clarify if the pipe is being sized using Table 6-4 or Appendix A of the 1994 UPC.
5. Provide upper terminal cleanouts on horizontal drainage pipes over 5 feet in length and for all sinks. Reference Section 707.4, UPC 1994. See P1 and P11 in room 142 and P8 in room 106.
6. Size the natural gas pipe using Table 12-3, UPC or provide calculations demonstrating conformance to Section 1217.3, UPC 1994. The reply to this comment was unclear. If alternate pipe sizing calculations have been used, please provide them. If Table 12-3 is being used, follow the sizing directions shown in Section 1217.2.
7. The information provided regarding the Vetroson Active Anesthesia Scavenger does not show that the system and its installation complies with the requirements of NFPA 99, Chapter 4 (1996 edition) or that the unit is even Listed or Labeled. Reference Appendix F, UPC 1994, as amended by the State of Arizona.
8. The "AE Piping Detail" is not shown on sheet P500. Provide a detail showing the support of the WAGD piping and ceiling mounted inlets as noted in keynote 2 on sheet P102.
9. Special Inspection of the medical gases (e.g. oxygen) and the WAGD system is required. See the attached Special Inspection Certificate, which must be submitted before the permit is issued. Reference Section 306, Uniform Administrative Code, 1997.
04/05/2005 GERRY KOZIOL WWM REVIEW Denied needs manhole tap permit. needs wastewater-iwc review- Tom Tomchak- 579-5771. Exterior trench drains on west side of building may not prevent wastewater intrusion into public sewer.
04/12/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 1. "Ckt B-34,36 for receptacle for future X-Ray. Pls confirm that this is plug-in equipment which does not need a disconnect." This comment was made on the first submittal. Please address.
2. Ckt B-14,16 powers F-1. Mechanical M100 Keyed Note 14 calls for a 5KW, 240V 3-phase unit. Electrical calls for a 3.3 KW, 208V, single phase unit. Pls coordinate with Mechanical and clarify.
3. Provide conductor size for compressor on B-37,39.
4. Phone System Diagram Sheet E600 refers to "NEC2002 830D". There is no NEC2002 830D. The reference intended for this purpose may be NEC 800.40 (B) (1).
5. Specifications 16450 call for only two service ground electrodes, the water piping system and a Ufer as made electrode. This does not correspond to Grounding System Diagram on Sheet E601. Please coordinate and clarify, noting the requirements of NEC 250.50 (A) (3).
6. Please submit catalogue cut sheets for Fixtures M and L1. All exterior fixtures shall comply with the Lighting Ordinance http://www.ci.tucson.az.us/dsd/Codes___Ordinances/Outdoor_Lighting_Code.pdf and be clearly listed for damp or wet locations as appropriate. Exterior Lighting per 2002 IECC 805.5.
7. Submit Lighting Power Budget per Table 805.4.2 2000 IECC.
8. Panel Schedule powers Hoist in Room 119 on Ckt B-31. On Electrical Power Plan B-31 is in Surgery, Room 123. Please clarify.
9. Panel Schedule powers Surgical Lights in Room 123 on Ckt B-28. On Electrical Power Plan B-28 is in Stall #1, Room 119. Please clarify.
10. Reference Sheet P102 Keynotes 2 & 3, and Sheet E101 Keynote 6. It appears that the use of a receptacle concealed above the ceiling grid for connection of the Anesthesia Scavenger Power Unit would be in violation of NEC 400.8 (5).
04/19/2005 DAVID RIVERA ZONING REVIEW Denied Zoning cannot approve the building plans at this time. Please include two copies of the approved site plan, landscape plan and NPPO with the next submittal.

David Rivera
Zoning Review Section
April 19, 2005

Final Status

Task End Date Reviewer's Name Type of Review Description
04/19/2005 DHERRON1 OUT TO CUSTOMER Completed
04/19/2005 DHERRON1 REJECT SHELF Completed