Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM04322
Parcel: 11005014C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM04322
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation calculations for the project.
Reference Section 403.3, IMC 2000.
2. Provide calculations to show how the proposed
ductwork meets the manufacturer's listing requirements
for proper operation of the equipment. Reference
Section 106.3.1, IMC 2000.
10/08/2004 GERRY KOZIOL WWM REVIEW Passed
10/13/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
10/14/2004 CAGUILA1 ZONING REVIEW Needs Review