Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM04322
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/08/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide ventilation calculations for the project. Reference Section 403.3, IMC 2000. 2. Provide calculations to show how the proposed ductwork meets the manufacturer's listing requirements for proper operation of the equipment. Reference Section 106.3.1, IMC 2000. |
| 10/08/2004 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 10/13/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/14/2004 | CAGUILA1 | ZONING | REVIEW | Needs Review |