Permit Number: T04CM04322
Parcel: 11005014C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04322
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
09/29/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/29/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Needs Review BEFORE AN O.K. TO SUBMIT I RECOMMEND THE FOLLOWING INFORMATION SHOULD BE PROVIDED.
1) CODE REVIEW CHECK LIST
2) RAMP DOES NOT MEET THE ANSI A117.1 STANDARDS. SECTION 405.2
3) LOCATE AND DIMENSION ACCESSIBLE RESTROOMS ON DRAWINGS.
4)CLARIFY OCCUPANCY AND SEPERATION REQUIREMENTS FOR ALL SURROUNDING TENANTS INCLUDING THE SECOND FLOOR.
5)CLARIY ACCESSIBILITY FOR IBC AND ANSI 117.1 OR CALCULTIONS FOR 20% COST.
09/29/2004 ROBERT SHERRY WATER REVIEW Approved
09/29/2004 JIM EGAN FIRE REVIEW Approved
09/29/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The governing code for the mechanical work is the 2000 IMC, not the 2000 IBC.
2. Provide ventilation calculations for the project. Reference Section 403.3, IMC 2000.
3. Provide operating information for the existing heat pumps and exhaust fan (e.g. airflow capacity, electrical data)
4. Provide calculations to show how the proposed ductwork meets the manufacturer's listing requirements for proper operation of the equipment. Reference Section 106.3.1, IMC 2000.
09/29/2004 MARTIN HAEBERLE ELECTRICAL-COMMERCIAL REVIEW Approved
10/08/2004 DROBEY1 WWM REVIEW Needs Review
10/08/2004 DROBEY1 ZONING REVIEW Needs Review