Permit Number: T04CM04284
Parcel: 12108053A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04284
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/24/2004 JIM EGAN FIRE REVIEW Approved
09/24/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Based on the submitted calculations, a 1/2" water line can support approximately 3 fixture units. Verify the availability of a suitable source for the water and show it on the drawing. Reference Section 103.2.3, UPC 1994.
2.Show the layout of the waste piping to demonstrate that adding the sink will not result in overloading any section of the existing waste piping. Reference Section 103.2.3, UPC 1994.
09/24/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
09/24/2004 ROBERT SHERRY WATER REVIEW Approved
09/24/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the waiting/reception area receives the minimum amount of outside air based on Table 403.3, IMC 2000.
09/27/2004 DAVID RIVERA ZONING REVIEW Approved
09/27/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE METAL STUD BRACING FOR INTERIOR PARTITION. METAL STRAP IS NOT A APPROVED METHOD.
09/27/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
10/06/2004 TACHONG1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/06/2004 TAMI ACHONG OUT TO CUSTOMER Completed